The Amprobe DM-5 Power Quality Analyzer allows you to easily and quickly discover the source and magnitude of power quality issues. At half the size of previous models, the compact DM-5 brings speed and efficiency to power quality jobs ranging from routine maintenance to in-plant troubleshooting of individual machinery and power distribution panels. The DM-5 software provides a full analysis with multiple data visualization options that allows you to quickly visualize your recorded data to identify potential issues. Built for use in even the largest facilities, the DM-5 is safety tested to meet the world’s most prestigious safety standards and is rated to CAT IV 300 V, CAT III 600 V, CAT II 1000 V.
Pico Labs Ltd. offers top-notch electrical product rental and calibration services. Our expert team ensures accurate and reliable solutions for your Power & Energy projects. Save costs, improve efficiency, and trust the precision of our services to keep your operations running smoothly with state-of-the-art electrical instruments.
| Features | DM-5 Power Quality Analyzer |
| Wiring connection | 1P2W, 1P3W, 3P3W, 3P4W |
| Measurements and parameters | Voltage, current, frequency, active power, reactive power, apparent power, active energy, reactive energy, apparent energy, power factor (cos ø), neutral current, demand, harmonics, quality (swell/dip/interruption, transients/overvoltage, inrush current, unbalance rate), capacitance calculation for PF correction unit, flicker |
| Voltage (rms) | Range: 600.0 / 1000 V Accuracy: ±0.2% + 0.2%f.s.(sine wave, 40 Hz to 70 Hz) Allowable input: 1% to 120% of each range (rms). 200% of each range (peak) Display range: 0.15% to 130 % of each range Crest factor: 3 or less Sampling speed of voltage transient: 24 μs Input impedance: approx. 1.67 MΩ |
| Current (rms) | Accuracy: ±0.2% + 0.2%f.s. + accuracy of flex current sensor (sine wave, 40 Hz to 70 Hz) Allowable input: 1% to 110% of each range (rms). 200% of each range (peak) Display range: 0.15% to 130 % of each range Crest factor: 3 or less Input impedance: approx. 100 kΩ |
| Swell / dip / interruption | Range: same as Voltage (rms) Accuracy: ±1.0% of nominal voltage Threshold value: In percentage of nominal voltage value |
| Power and energy | CT-53 flex current sensor (3-ch): max. 6000 kW CT-500 flex current sensor (1-ch): max. 1000 kW Active power accuracy: ±0.3% + 0.2%f.s. + accuracy of flex current sensor (PF 1, sine wave, 40 Hz to 70 Hz) Influence of power factor: ±1.0% (PF 0.5, 40 Hz to 70 Hz ) Wh: 0.00000 mWh to 9999.99 TWh VAh: 0.00000 VAh to 9999.99 TVAh varh: 0.00000 varh to 9999.99 Tvarh |
| Power factor | Display range: -1.000 to 0.000 to 1.000 Accuracy: ±1dgt against each calculated value (for sum: ±3dgt) |
| Harmonics | Harmonics order (n): 1 to 50th Inter-harmonics order (n): 1 to 50th Volts: 0.0% to 100.0%, accuracy (≥3% at 100 V nominal voltage): ±10% accuracy (<3% at 100 V nominal voltage): ±0.3% of nominal voltage accuracy (1000 V range): ±0.2% + 0.2%f.s Amps: 0.0% to 100.0%, accuracy (≥10% to max. input range): ±10% + flex current sensor accuracy (<10% to max. input range): ±1.0% + flex current sensor Watts: 0.0% to 100.0%, accuracy: ±0.3% + 0.2%f.s. + accuracy of flex current sensor (PF 1, sine wave, 50/60 Hz) THD: 0.0% to 100.0%, Phase angle: 0.0° to ± 180° |
| Flicker | Displayed items: Pst(1min), Pst, Plt, Max Pst, Max Plt, V, time left Measurement method: Complied with IEC 61000-4-30 and IEC 61000-4-15 Ed.2 Accuracy: Pst (max.20): ±10% according to IEC 61000-4-15 |
| Unbalance | Volts: 0.00% to 100.00%, accuracy: ±0.3% at 50/60 Hz, sine wave (0.00% to 5.00% according to IEC 61000-4-030) Current: 0.00% to 100.00% |
| Transient | Approx. 40.96 ksps (every 2.4 μs) Range: 50 V to 2200 Vdc Accuracy: ±0.5% at 1000 Vdc |
| Inrush current | Range: same as Current (rms) Accuracy: ±0.4% + 0.4%f.s. + accuracy of flex current sensor Threshold value: In percentage of the measurement range |
| Capacitance | Range: 0.000 nF to 9999 F, 0.000 kvar to 999 kvar |
| Specifications | |
| Display | 3.5inch, TFT, QVGA(320xRGBx240) |
| Display update | Every 1 second* *There may be time lag in display update (max. 2 seconds) due to arithmetic processing. However, no time lag between the recorded data and the time stamp |
| Operating temperature and humidity | 32°F to 104 °F (0 °C to 40 °C), ≤ 85 %RH (no condensation) Guaranteed accuracy at 73 °F ± 9 °F (23 °C ± 5 °C), ≤ 85 %RH (no condensation) |
| Operating altitude | 0 to 6,561 ft (0 to 2,000 m) |
| Pollution degree | 2 |
| Dust/water proof | IP 40 |
| Drop proof | 3.3 ft (1 m) |
| Storage temperature and humidity | -4 to 140 °F (-20 °C to 60 °C), ≤ 85 % RH (no condensation) |
| Power supply | Battery: 6 x AA 1.5 V Alkaline battery (LR6) AC power supply: AC100 V to AC 240 V, 50 Hz to 60 Hz, 7 VAmax |
| Battery life | 3 hours (typical) Current consumption: 1.0 A at 3.0 Vdc (typical) |
| EMC | Meets EN 61326-1 |
| Safety compliance | UL/IEC 61010-1, IEC 61010-031, IEC 61010-2-030 |
| Power quality measurement | Complies with IEC 61000-4-030 ed.2 Class S |
| Certifications | ![]() ![]() ![]() |
| Dimensions (L x W x D) | 6.9 x 4.7 x 2.7 in (17.5 X 12 X 6.8 cm) |
| Weight | Approx. 2.0 lb (900 g) with batteries installed |